The details of the medium voltage current limiting reactor part number 6080CLR is shown below. The medium voltage current limiting reactor is rated for 7200 VAC, 50 Hz, 630 Amps continuous. Three inductor are required for one CLR application.
Three inductors are required for one CLR application.
Only one inductor is shown above.
The photo of a similar enclosure is shown below for reference:
All our medium voltage current limiting inductors are custom built to order. Let us know the continuous current and fault limiting current to design a medium voltage current limiting inductor which is suitable for your application. To discuss your specific application, please call us toll free at (800) 595-7096, or send us an email at info@lcmagnetics.com.
Specifications:
- Medium Voltage Current Limiting Reactor, P/N 6080CLR
- Rating: 7200 VAC, 50 Hz, 630 Amps
- Inductance: 661.51 µH ± 25 per short circuit study
- Fault Current or CLR current: 20,000 Amps
- Copper bus bar: 3” x ⅜” with two holes.
- Open core and coil: 25” H x 40” W x 40” D
- IP 20 Enclosure: 90” H x 90” W x 50” D
- All connections are inside the enclosure.
The customer application is shown below:
The voltage drop across the current limiting inductor at different current levels is shown in Table A:
Related Links:
- http://www.lcmagnetics.com/inductors/current-limiting-reactor/high-voltage-current-limiting-reactor-clr-630-amps-pn-6080l
- http://www.lcmagnetics.com/inductors/current-limiting-reactor/current-limiting-reactor-700-amps-continuous-60-hz-pn-18814l
- http://www.lcmagnetics.com/inductors/current-limiting-reactor/currernt-limitting-reactor-800-a-60-hz-pn-18794l
All our medium voltage current limiting inductors are custom built to order. Let us know the continuous current and fault limiting current to design a medium voltage current limiting inductor which is suitable for your application. To discuss your specific application, please call us toll free at (800) 595-7096, or send us an email at info@lcmagnetics.com.
No comments:
Post a Comment