December 20, 2013

Three Phase 2000 Amp Transformer, 7 KVA, Output 2 VAC 2000 Amps, P/N 18777U

Product Overview:

The details of the three phase high current transformer, 7 KVA part number 18777U is shown below. Input is 68 VAC, 3 PH, 60 Hz. Output 2 VAC at 2000 Amps, 3 PH, 60 Hz.




Three Phase High Current Transformer

Specifications:


  • Three Phase Transformer 7 KVA, 3 PH, 60 Hz, P/N 18777U 
  • Primary 68 VAC L-L, 39.26 VAC L-N, 60 Amps, Wye, 1600 circular mils per amp 
  • Secondary 2 VAC L-L, 1.1547 VAC L-N, 2000 Amps, Wye, 1469 circular mils per amp 
  • Secondary winding: 3 twin x 22 to provide 1469 circular mils per amp 
  • Open core and coil: 15”W x 12.5”H x 17”D approximately 
  • Primary bus bars are 1” x 0.25” copper bus bar. 
  • Secondary bus bars are 4” x 0.375” copper bus bar. 
  • Guidelines: 1 square inch per 1000 amps copper cross section 
  • Temperature rise: 80 degrees C maximum