2500 Amp Transformer, 120 KVA, Output 48 VAC 2500 Amps, P/N 19009NU

Product Overview

The details of the single phase 2500 amp transformer, part number 19009NU is shown below. Primary is 480 VAC, 250 Amps. Secondary is 48 VAC, 2500 Amps. The unit is housed inside an indoor enclosure. 




2500 Amp High Current Transformer

Specifications:

  • High Current Transformer 120 KVA, 1 PH, 60 Hz, P/N 19009NU 
  • Primary: 480 VAC, 250 Amps 
  • Primary turns are 71 turns and placed over the secondary turns 
  • Primary copper bus bars are 1/4” x 1” with one hole 
  • Secondary: 48 VAC ± 5 %, 2500 Amps 
  • Secondary turns are 7.5 turns and wound first 
  • Secondary copper bus bars are 3/8” x 4” with four holes 
  • Turn ratio: 1 to 9.845 
  • Copper winding construction 
  • Indoor enclosure: 50”H x 36”W x 26”D

4000 Amp Transformer, 32 KVA, Output 8 VAC 4000 Amps, P/N 19005U

Product Overview
The details of the 4000 amp single turn transformer, part number 19005 is shown below. Primary is 220/230/240/250 VAC, 1 PH, 60 Hz. Secondary is 8 VAC, 8000 Amps.




4000 Amp High Current Transformer

Specifications:

  • High Current Transformer 32 KVA, 1 PH, 60 Hz, P/N 19005U
  • Primary: 220/230/240/250 VAC, 145 Amps max
  • Secondary: 8 VAC, 4000 Amps, 1 turn of customer supplied bus bar
  • Window provided for customer bus bar: 5" x 5"
  • Primary copper bus bar: 1/4" x 1" with one hole
  • Estimated dimensions: 16"H x 23"W x 17"D
  • If 250 VAC is applied on input 1 and 2, output 6 and 7 is 9.2 VAC approximately. 
  • Estimated weight: 600 lbs approx.

200 Amp High Current Transformer, 0.5 KVA, Output 2.5 VAC 200 Amps,

Product Overview:

The details of the single phase 200 amp transformer, 0.5 KVA part number 18812U is shown below. Input is 1.25 / 12.5 VAC, 1 PH, 60 Hz. Output 2.5 VAC at 200 Amps, 1 PH, 60 Hz.



High Current Transformer 0.5 KVA

Specifications:

  • Transformer 0.5 KVA, 1 PH, 60 Hz, P/N 18812U
  • Primary: 1.25 / 12.5 VAC, 40 Amps
  • Secondary: 2.5 VAC, 200 Amps
  • Open Core & Coil
  • Dimensions: 6” H x 5.25” W x 8” D, approximately
  • Input bus bars are ⅛” x ⅝” with 1 hole.
  • Output bus bars are 1” x ¼” with 1 hole
  • Turn ratio 5:1 and 1:2


High Current 3000 Amp Transformer, 24 KVA, Output 8 VAC 3000 Amps, P/N 18420

Product Overview:

The details of the single phase 300 amp transformer, 24 KVA part number 18420U is shown below. Input is 240 VAC, 1 PH, 60 Hz. Output 8 VAC at 3000 Amps, 1 PH, 60 Hz.




High Current 800 Amp Transformer

Specifications:


  • Transformer: 24 KVA, 1 PH, 60 Hz, P/N 18420U 
  • Primary: 480 VAC, 50 Amps 
  • Secondary: 8 VAC, 3000 Amps 
  • Open Core & Coil 
  • Dimensions: 12.5” H x 15” W x 25”D 
  • Weight: 300 lbs approx. 
  • Output bus bars are 4” x 5” x ¾” with one 9/16” dia. Hole 
  • Force cooling may be required

500 Amp Transformer, 4 KVA, Output 8 VAC 500 Amps, P/N 18866U

Product Overview:

The details of the single phase 500 amp transformer, 4 KVA part number 18866U is shown below. Input is 480 VAC, 1 PH, 60 Hz. Output 8 VAC at 500 Amps, 1 PH, 60 Hz.





High Current 500 Amp Transformer

Specifications:

  • 4 KVA High Current Transformer: 1 PH, 60 Hz, P/N 18866U
  • Primary: 480 VAC, 8.33 Amps 
  • Secondary: 8 VAC, 500 Amps 
  • Open Core & Coil, dimensions: 10”H x 12” W x 8”D approximately 
  • Primary copper bus bars are 1/8” x 5/8” with one hole. 
  • Secondary Copper bus bars are 1 1/2” x 1/4” with one hole. 
  • Weight: 115 lbs approximately


Related Links:




L/C Magnetics on LinkedIn
L/C Magnetics on Facebook

L/C Magnetics on Google Plus


All our three phase high current transformers are custom built to order. To discuss your specific application, please call us toll free at (800) 595-7096, or send us an email at info@lcmagnetics.com.

800 Amp Transformer, 4 KVA, Output 5 VAC 800 Amps, P/N 18433U

Product Overview:

The details of the single phase 800 amp transformer, 4 KVA part number 18433U is shown below. Input is 220 VAC, 1 PH, 60 Hz. Output 5 VAC at 800 Amps, 1 PH, 60 Hz.





High Current 800 Amp Transformer

Specifications:

  • High Current Transformer 4 KVA, 1 PH, 60 Hz, P/N 18433
  • Primary: 220 VAC, 20 Amps
  • Secondary: 5 VAC, 800 Amps
  • Open Core & Coil
  • Dimensions: 16” H x 9” W x 11”D
  • Weight: 97 lbs approx. 
  • Output bus bars are 4” x 5” x ⅜” with two holes
  • Force cooling may be required

High Current Center Tapped Transformer, 4 KVA, Output 5/10 VAC 400 Amps, P/N 18782U

Product Overview:

The details of the high current center tapped transformer, 7 KVA part number 18777U is shown below. Input is 208 VAC, 1 PH, 60 Hz. Output 5/10 VAC at 400 Amps, 1 PH, 60 Hz.



Center Tapped 400 Amp Transformer

Specifications:

  • High Current Transformer 4 KVA, 1 PH, 60 Hz, P/N 18782U
  • Primary: 208 VAC, 20 A
  • Secondary: 5/10 VAC, 400 Amps max
  • Open Core & Coil
  • Dimensions: 10” H x 9” W x 12” D
  • Primary bus bars are ⅛” x ⅝” 
  • Secondary bus bars 1 ½” x ¼” with one ⅜” diameter Hole
  • Forced cooling may be required

Related Links:




L/C Magnetics on LinkedIn
L/C Magnetics on Facebook

L/C Magnetics on Google Plus


L/C Magnetics is a high current transformer manufacturer. For your specific high current requirements please call us toll free at (800) 595-7096 or send us an e-mail at info@lcmagnetics.com.

December 20, 2013

Three Phase 2000 Amp Transformer, 7 KVA, Output 2 VAC 2000 Amps, P/N 18777U

Product Overview:

The details of the three phase high current transformer, 7 KVA part number 18777U is shown below. Input is 68 VAC, 3 PH, 60 Hz. Output 2 VAC at 2000 Amps, 3 PH, 60 Hz.




Three Phase High Current Transformer

Specifications:


  • Three Phase Transformer 7 KVA, 3 PH, 60 Hz, P/N 18777U 
  • Primary 68 VAC L-L, 39.26 VAC L-N, 60 Amps, Wye, 1600 circular mils per amp 
  • Secondary 2 VAC L-L, 1.1547 VAC L-N, 2000 Amps, Wye, 1469 circular mils per amp 
  • Secondary winding: 3 twin x 22 to provide 1469 circular mils per amp 
  • Open core and coil: 15”W x 12.5”H x 17”D approximately 
  • Primary bus bars are 1” x 0.25” copper bus bar. 
  • Secondary bus bars are 4” x 0.375” copper bus bar. 
  • Guidelines: 1 square inch per 1000 amps copper cross section 
  • Temperature rise: 80 degrees C maximum


December 19, 2013

Multi Tap Transformers, 139 KVA, P/N 18781NU, Input 240 VAC, Output 240/480 VAC

Product Overview

The photo of a three phase center tapped transformers, 139 KVA, part number 18781NU is shown below. The unit is housed inside an indoor enclosure. 




Three Phase Transformer 139 KVA

Specifications:

  • Transformer: 139 KVA, 3 PH, 60 Hz, P/N 18781NU 
  • Primary: 208 VAC, 3 PH, Delta, 385 Amps, no taps 
  • Secondary Tap 1: 240 VAC, 3 PH, Wye, 162 Amps, 68 KVA 
  • Secondary Tap 2: 480 VAC, 3 PH, Wye, 85 Amps, 71 KVA 
  • Indoor enclosure: 50” H x 36” W x26” D, floor mount 
  • Both Tap 1 and Tap 2 can be used simultaneously 
  • Copper bus bars are 2” x ¼” with one hole 
  • All Input/output connections are inside the enclosure

Four Secondary Winding Transformer, 115 VA, P/N 18749U

Product Overview


The photo of a single primary multiple four secondary Transformer, 115 VA, part number 18749U is shown below. Primary side is a single winding. Secondary side has four windings.




Four Winding Transformer, 115 VA

Specifications:


  • Multi Tap Transformer: 115 VA, 1 PH, 60 Hz, P/N 18749 
  • Primary (A, B): 240 VAC, 0.5 Amps 
  • Secondary (C, D): 24 VAC, 1 Amp 
  • Secondary (E, F): 26 VAC, 1.5 Amp 
  • Secondary (G, H): 6 VAC, 5 Amp 
  • Secondary (I, J): 220 VAC, 0.1 Amp 
  • Open Core and Coil: 4.5” W x 4”H x 3.5”D

Dual Secondary Winding Transformer, 6 KVA, P/N 18721U

Product Overview


The photo of a single primary multiple dual secondary Transformer, 6 KVA, part number 18721U is shown below. Primary side is a single winding. Secondary side has two windings.




Dual Winding Transformer, 6 KVA

Specifications:


  • Multi Tap Transformer 6 KVA, 1 PH, 60 HZ, P/N 18721U
  • Primary: 208 VAC, 1 PH, 60 Hz 
  • Secondary (X1, X2): 60 VAC, 1 PH, 60 HZ 
  • Secondary (X3, X4): 60 VAC, 1 PH, 60 Hz 
  • Open core and Coil, 9” H x 9” W x 9” D approximately 
  • Input/output bus bars are: 1/8” x 5/8” with one hole


December 18, 2013

Multiple Secondary Winding Transformer, 7.5 KVA, P/N 19017AU

Product Overview


The photo of a single phase multiple secondary Transformer, 7.5 KVA, part number 19017AU is shown below. Primary side is a single winding. Secondary side has two windings.




Single Phase Multiple Winding Transformer

Specifications:
  • Multi Tap Transformer 7.5 KVA, 1 PH, 60 Hz, P/N 19017AU 
  • Primary: 480 VAC, 16 Amps, terminals (1, 2) 
  • Secondary 1: 160 VAC, 24 Amps, terminals (3, 4) 
  • Secondary 2: 160 VAC, 24 Amps, terminals (5, 6) 
  • Copper bus bars: 1/8” x 5/8” with one hole 
  • Open core & coil, 9”H x 9”W x 9”D approx. 
  • Copper winding construction 
  • Weight: 100 lbs approx.


December 16, 2013

400 Hz Gapped Inductor, 57 Amps, P/N 18786L1

Product Overview

The details of the  military power inductor part number 18786L1 is shown below:




400 Hz Power Inductor


Specifications:


  • 57 amp 400 Hz Inductor, P/N 18786L1
  • Inductance L (1, 2) = 107 uH ± 25%, 57 Amps
  • RDC = 0.00155 ohms
  • Calculated core loss: 27.5 watts
  • Calculated copper loss: 5 watts
  • Temperature rise: 35 degrees C
  • Open core and coil: 5″ H x 5″ W x 5″ D
  • Copper bus bar: ⅛” x ⅝” with a hole

Military Power Transformer, 12 KVA, P/N 18700

Product Overview

The details of the military power transformer, part number LC-1152 is shown below. 




Military 400 Hz Transformer

Specifications:



  • 12 KVA 400 Hz Transformer: , 3 PH, P/N 18700
  • Input: 200 VAC L-L, 35 A, Wye
  • Output: 115 VAC L-L, 60 A, Delta
  • Frequency: 400 Hz
  • Open core and coil: 11″ H x 14.5″ W x 8″ D
  • Copper winding construction